Los Angeles department of building safty logo Permit and Inspection Report banner
620 N STONE CANYON ROAD 90077
APPLICATION / PERMIT NUMBER: 09043-20000-01600
PLAN CHECK / JOB NUMBER: M09VN00992

Plan Check and Permit Information


GROUP: Mechanical
TYPE: Fire Sprinkler
SUB-TYPE: 1 or 2 Family Dwelling
PRIMARY USE: N/A
WORK DESCRIPTION: (1) NEW PRIVATE FIRE HYDRANT AND 6" UNDERGROUND FOR A SINGLE-FAMILY DWELLING. 32' ELEVATION DIFFERENCE BETWEEN NEW 6" FIRE SERVICE DETECTOR CHECK VALVE AND HYDRANT OUTLET. FIRE DEPT REQUIRES 1400 GPM AT 20 PSI AT THE HYDRANT. AVAILABLE MAX PRESSURE: 159 PSI; STATIC MIN: 149; RESIDUAL AT 1400 GPM FLOWING: 132 PSI PER SAR.
PERMIT ISSUED: Yes PERMIT ISSUE DATE: 07/24/2009 ISSUING OFFICE: Van Nuys
CURRENT STATUS: Permit Finaled CURRENT STATUS DATE: 05/15/2014

Permit Application Status History
Submitted 07/24/2009 MANUEL HERNANDEZ
Assigned to Plan Check Engineer 07/24/2009 MANUEL HERNANDEZ
Issued 07/24/2009 LADBS
Permit Finaled 05/14/2014 THOMAS COWAN

Permit Application Clearance Information
  No data available

Licensed Professional/Contractor Information
Contractor Information
Kennco Plumbing Inc; Lic. No.: 595570-C16
26575 RUETHER AVE
SANTA CLARITA, CA  91350

Inspection Activity Information

Inspector Information
JORDAN PIVNIK, (310) 914-3955
Office Hours: 7:00-8:00 AM MON-FRI

Pending Inspection Request(s)
  No data available

Inspection Request History
  Fire Dept Connection Hydro   09/18/2009   Corrections Issued   JOHN ZAVALA
  Underground Hydro   09/18/2009   Corrections Issued   JOHN ZAVALA
  Underground Hydro   09/29/2009   Partial Inspection   JOHN ZAVALA
  Underground Hydro   10/01/2009   Partial Approval   JOHN ZAVALA
  Rough   10/20/2009   Corrections Issued   JOHN ZAVALA
  Underground Hydro   10/20/2009   Corrections Issued   JOHN ZAVALA
  Fire Pump Test   10/22/2009   Not Ready for Inspection   JOHN ZAVALA
  Underground Hydro   10/22/2009   Approved   JOHN ZAVALA
  Overhead Hydro   02/28/2011   Not Ready for Inspection   TODD JENKINS
  Rough   02/28/2011   Corrections Issued   TODD JENKINS
  Special/Order Compliance   03/01/2011   Partial Inspection   TODD JENKINS
  Overhead Hydro   03/02/2011   Corrections Issued   TODD JENKINS
  Overhead Hydro   03/02/2011   Partial Approval   DANIEL SANCHEZ
  Rough   03/02/2011   Corrections Issued   TODD JENKINS
  Rough   03/02/2011   Partial Approval   DANIEL SANCHEZ
  Rough   03/03/2011   Corrections Issued   TODD JENKINS
  Overhead Hydro   03/30/2011   Partial Approval   TODD JENKINS
  Rough   03/30/2011   Partial Approval   TODD JENKINS
  Overhead Hydro   04/21/2011   Partial Approval   TODD JENKINS
  Rough   04/21/2011   Corrections Issued   TODD JENKINS
  Overhead Hydro   04/25/2011   Partial Approval   TODD JENKINS
  Rough   04/25/2011   Partial Approval   TODD JENKINS
  Rough   05/11/2011   Partial Approval   DANIEL SANCHEZ
  Underground Flush   08/17/2011   Partial Approval   TODD JENKINS
  Overhead Hydro   10/31/2011   Partial Approval   TODD JENKINS
  Rough   10/31/2011   Corrections Issued   TODD JENKINS
  Overhead Hydro   11/02/2011   Partial Approval   TODD JENKINS
  Rough   11/02/2011   Partial Approval   TODD JENKINS
  Overhead Hydro   11/22/2011   Partial Approval   TODD JENKINS
  Rough   11/22/2011   Partial Approval   TODD JENKINS
  Overhead Hydro   12/20/2011   Partial Approval   TODD JENKINS
  Rough   12/20/2011   Corrections Issued   TODD JENKINS
  Overhead Hydro   01/06/2012   Partial Inspection   TODD JENKINS
  Rough   01/06/2012   Partial Inspection   TODD JENKINS
  Rough   01/12/2012   Partial Approval   TODD JENKINS
  Overhead Hydro   02/10/2012   Not Ready for Inspection   TODD JENKINS
  Overhead Hydro   02/13/2012   Partial Approval   TODD JENKINS
  Rough   02/13/2012   Partial Approval   TODD JENKINS
  Underground Hydro   04/09/2012   Partial Approval   TODD JENKINS
  Underground Flush   04/16/2012   Partial Approval   TODD JENKINS
  Rough   10/10/2012   Partial Inspection   THOMAS COWAN
  Underground Hydro   10/10/2012   Partial Inspection   THOMAS COWAN
  Rough   10/11/2012   Not Ready for Inspection   THOMAS COWAN
  Underground Hydro   05/13/2013   Corrections Issued   THOMAS COWAN
  Underground Hydro   05/22/2013   Partial Approval   THOMAS COWAN
  Underground Hydro   07/03/2013   Approved   THOMAS COWAN
  Underground Flush   07/11/2013   Approved   THOMAS COWAN
  Overhead Hydro   11/06/2013   Partial Approval   THOMAS COWAN
  Rough   11/06/2013   Partial Approval   THOMAS COWAN
  Final   03/12/2014   Partial Approval   THOMAS COWAN
  Final   05/14/2014   Permit Finaled   THOMAS COWAN

BACK     NEW SEARCH