GROUP: |
Mechanical |
TYPE: |
Fire Sprinkler |
SUB-TYPE: |
1 or 2 Family Dwelling |
PRIMARY USE: |
N/A |
WORK DESCRIPTION: |
(1) NEW PRIVATE FIRE HYDRANT AND 6" UNDERGROUND FOR A SINGLE-FAMILY DWELLING. 32' ELEVATION DIFFERENCE BETWEEN NEW 6" FIRE SERVICE DETECTOR CHECK VALVE AND HYDRANT OUTLET. FIRE DEPT REQUIRES 1400 GPM AT 20 PSI AT THE HYDRANT. AVAILABLE MAX PRESSURE: 159 PSI; STATIC MIN: 149; RESIDUAL AT 1400 GPM FLOWING: 132 PSI PER SAR. |
PERMIT ISSUED: |
Yes |
PERMIT ISSUE DATE: |
07/24/2009 |
ISSUING OFFICE: |
Van Nuys |
CURRENT STATUS: |
Permit Finaled |
CURRENT STATUS DATE: |
05/15/2014 |
|
|
Submitted |
07/24/2009 |
MANUEL HERNANDEZ |
Assigned to Plan Check Engineer |
07/24/2009 |
MANUEL HERNANDEZ |
Issued |
07/24/2009 |
LADBS |
Permit Finaled |
05/14/2014 |
THOMAS COWAN |
|